Mn/300/100 fire alarm control panel
Overview
The mn300 is a new type of analog fire alarm control panel which has 100 alarm control points (detectors and modules which are characterized by fully mixed coding, non-polarity and two buses). It complies with the provisions of both fire alarm control units (gb4717-2005) and automatic control system for fire protection (gb16806-2006).
Features
1 the intelligent detectors and the intelligent modules have internal microprocessors to realize digital filtering and auto-compensation functions; the data collection is true and reliable; the mn300 control panel can carry out data processing based on fuzzy control theory and modern fire alarm theory to fundamentally avoid missing alarms and to reduce false alarms, so as to improve reliability.
2 the detectors have a sensitivity setup function and can adjust the alarm sensitivity according to the specific environment and their influences.
3 the detecting bus and the control bus share a two-wire structure and have non-polarity and fully mixed coding of the detectors and modules, and the intelligent detectors and the intelligent modules can be directly connected to them, which greatly simplifies the system wiring, engineering installation and circuit maintenance.
4 the system uses an ac-dc master-standby power supply system which will automatically change between the master and standby power supplies in the event of a power failure of either of the two power supplies to ensure uninterrupted operation of the system.
5 the mn300 can be connected to a special mini-printer to realize real-time printing.
6 the mn300 can be connected to floor fire display panels to display fire alarms by standard rs-485
7 the mn300 can be connected to ten multi-line linkage control/monitoring points to control and monitor important equipment.
8 the mn300 is equipped with eight bus manual control points, which makes it very easy for the user to control related equipment.
The 6001 analogue addressable control and indicating equipment forms the central part of a fire detection and alarm
System. The fully networkable 2-wire 6001 is compatible with numens addressable devices and can also be connected
To non-addressable devices when used with addressable input modules.
Default configuration programming facilitates out-of-box installation and rapid commissioning. A powerful and versatile
Cause-and-effect pc-based programming tool enables rapid customization with software for sites that
Require special operating features.
The 6001 comes standard with features that allows flexibility and expandability.
Single loop or 2-loop options available
Single loop, expandable to 2-loops available
Networkable, up to 4 control panels
Up to 125 addressable devices per loop
Automatic device detection on start-up
Automatic device type-code verification
2 independently programmable non-addressable a/v alarm output circuits
2 programmable fire alarm relay outputs
Fault relay output
Backlit lcd display providing 4 rows of 40 characters
16 zone fire alarm led indicators
3000 event history log
HS-SG109 Sound Strobe of notification appliances offers a wide range of Sound/strobes, for wall and ceiling applications, indoors and outdoors. They are designed to be used in 24 volt DC systems.
Supplier: Optical Smoke Detector, Addressable Fire Alarm System, Conventional Fire Alarm System, Addressable Fire Telephone System
, Voice Evacuation Control Panel And Speakers
, 12 Gas Fire Suppression System, Emergency Light System, Fire Pump System, Fire Hose And Fire Hose Reel Cabinet, Fire Proof Cable And Fire Pipe
AC POWER: 220VAC, 50 Hz.
BATTERY: Sealed lead-acid batteries only. Maximum charging circuit: 27.6VDC @ 0.8 amp for
normal flat charge. Maximum battery charger capacity: 18AH battery.
NOTE: Two 10AH batteries can be housed in the cabinet. Larger batteries require a separate
battery box.
Total DC24V system power: 3.0 amps.
Maximum current per NAC: 1.25 amps.
Maximum battery charging capability: 18 AH.
Resettable four-wire smoke detector power output.
Non-resettable power output.
Integral Form-A Alarm, Trouble and Supervisory relays, rated at: 2.0 amps @ 30 VDC
(resistive), 2.0 amps @ 30 VAC (resistive).
Power Supply: AC 240V 50/60Hz
Stand-by Battery: DC24V Sealed Maintenance-Free Lead-Acid Battery
Charging Voltage: DC26.4V Below 450mA Trickle Charging
Circuit Voltage: DC24V Short Circuit Voltage 5V below 32mA
Loop Resistance: Below 50+ back and forth
Detector Installation: No limit in the number of differential detector & constant-temperature detectors used; smoke detectors or electronic differential detectors; each ciruit can connect to a maximum of 16 smoke detectors (monitoring current for detectors: DC24V 40¦A)
Terminal Resistor: 10k+
Number of indicators: 1 time the number of panel circuits
Number of Local Alarm: 1 time the number of panel circuits.
Number of circuit & Dimension:
1L/2L/4L/5L/8L (330x280x120mm)
12L/16L(400x300x120mm)
24L(495x300x120mm).
Breakthru Solutions is a leading fire safety equipment's, fire fighting appliances dealers and suppliers in Bangalore. Get the best price for fire extinguisher, fire fighting appliances in Bangalore, India.