2-wire technology and analog signal output (4-20mA)
High accuracy in total ambient temperature range
Wide power supply range (voltage)
Easy programming (calibration) via HART modem
• Universal PC programmable (PCP)
• 2 wire technology, 4 to 20 mA analogue output
• High accuracy in total ambient temperature range
• Configuration during measurement using configuration kit
• Customer specific measurement range setting
• Wide measurement range, according to requirement
Field of application
• PC programmable (PCP) Temperature head transmitter for converting the input signal into a standard 4 to 20 mA analog output signal
• Input: Resistance thermometer (RTD) Pt100
• Configuration using a PC with MS180 configuration kit (MS180-PC).
Appearance and Size (in mm)
NOTE: When order, please specify the measuring range, we’ll offer programming tool if needed.
NCS-TT106 smart temperature module, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control.
Features
Support multiple thermal resistance and thermocouples
Thermal resistance supports 2/3/4-wire connection mode
Thermocouple can use cold end compensation function
Better accuracy: PT100 ±0.3 ; K-type ±0.4
Universally programmable for various input signals
Available protocols: HART /FF H1 /PROFIBUS PA
Parameter
The ZP series Temperature Transmitter is designed to meet common Single Point measurement application requirements. This transmitter can easily work with a variety of sensors (RTDs and thermocouples) and thermowells. It provided in a head mount configuration suitable for installation in a wide variety of connection heads and housings. A PC-programmable interface is available, providing an easy-to-use configuration method from any PC.
Basic temperature transmitter offers a reliable solution for temperature monitoring points, provides flexible and reliable performance in process environments, Excellent performance with low temperature drift and auto zero calibration, reducing the need for expensive extension wires and multiplexers.
Power Supply 8.5VDC~32VDC
Input Types 4-20mA / 20-4mA;
RTD(PT100,PT200,PT500,PT1000,Cu50);
R(0-400 ,0-4000 );
TC(K,E,S,B,R,J,T,N);
mV(-80-+80mV);
V(0-1V)
Output signal types 4-20mA or 0...1/5V, 0...1/10V
Response Time < 0.4S (0-90%,100%-10%)
Precision �±0.05%
Temp. Drift 0.01% per Celsius
Volt fluctuation influence �±0.005% X span / below V DC
Load Capacity < 700 in 24VDC; (mA output)
< 1060 in 36VDC (Volt output)
Isolation Strength AC1500v 1min between the input / output
IP Ranking Casing/Terminal IP50/IP20
Universal head transmitter for resistance thermometers (rtd), thermocouples, resistance and voltage transmitters, settable using a pc, for installation in a sensor head (form b), compatible tmt 181.
Areas of application
Pc programmable (pcp) temperature head transmitter for converting various input signals into an scalable 4 to 20 ma analogue output signal
Input:
Resistance thermometer (rtd)
Thermocouple (tc)
Resistance transmitter (ohm)
Voltage transmitter (mv)
Online configuration using pc with anl 181 configuration kit and pc-software anly win 2000 (compatible e+h readwin 2000)
Benefits at a glance
Universally pc programmable for various signals
Galvanic isolation
2 wire technology, 4 to 20 ma analogue output
High accuracy in total ambient temperature range
Fault signal on sensor break or short circuit, presettable to namur ne 43
Emc to namur ne 21, ce
Ul recognized component to ul 3111-1
Ship building approval gl
Online configuration during measurement using setup connector
Output simulation
Customer specific measurement range settings or expanded setup
Technical data
Input: Rtd, tc, ohm, mv
Output: 4 to 20 ma
Supply voltage: 8 to 35 v dc (non-ex-area)
8 to 30 v dc (ex-area)
Operation: Pcp (pc programmable)
Installation: Sensor head form b
Field housing