UL2464 Wire and Cable
Applications:
As measuring, monitoring and control cable, it is suitable for the places of machine tool manufacturing, complete equipment installation engineering, power station, refrigeratory equipment, OA equipment, data processing system and heating and air-condition system.
Properties:
Heat resistance, good insulation property, excellent chemical performance, extruding sheath
Standards: UL 758
Structure:
Conductor: fine strands of tinned copper wire, exellent corrosion resistance.
Insulation: special PVC
Colour: acc. to UL 758
Sheath: 80 heat-resistant flame-resistant PVC, pass VW-1 flame testing
Colour: black (RAL9005) green (RAL6018)
Orange(RAL2003) purple(RAL4001)
Or refer to customers requirement.
Technical data:
Rated voltage: 300V
Test voltage: 2000V
Temperature range: Fixed installation: -40--+80
Flexing installation: -10--+80
The minimum bending radius: Fixed installation: 4×external diameter
Flexing installation: 15×external diameter.
CE cable :H07V-U/H07V-R/H07V-K
Despription:
Related temperature :70C
Related voltage:300/300V
Reference standard:
DIN VDE 0281-3-2001 HD21.3S3:1995+A1:1999
Tinned or bare,stranded or solid copper conductor
PVC/T11 insulation
Application:
For power supply and lighting.
In rolls.
Detailed Product Description
Electrical Properties:
Related voltage U0/U: 1.5~2.5 mm2: 450/750 U0
The number of core: 3~48
Mechanical Properties:
The tensile strength: 2100N
The free suspend length: max.250M (can not be used for elevator).
Significant smaller bending radius compared to round cables.
Operating temperature: -10---70(for special use:40~105)
Loop diameter: natural loop (approx. 250~350mm)
Chemical Properties:
Weather resistance: good
Conductor resistance at 20: good
Insulation resistance at 70: medium
Acid resistance at 20: medium
For specific environmental conditions please refer to manufacturer.
Colour Code: In accordance with GB5023.6
Core: Black, Brown, Blue, numbered, 1GNYE
Outer sheath: Black.
Application: To be used in electric block, electrical motion facilities, hoisting devices. The jacket can be made according to different climate and situation. So it can be also used in the outdoor.
Reference standard: In accordance with GB5023.6-1997.
FLAT ELEVATOR CABLE
Properties:
The outer sheath is extensively resistant to oil and cooling liquid.
Standards:GB5023.6,IEC60227-6,EN 50214
Structure:
Conductor: fine strands of bare copper wire,
Acc.to VDE0295 CLASS5
Insulation:special PVC
Colour:yellow,white,orangeg with black number with white digital coding
Bearing:steel rope
Outer sheath:flexible PVC,cold resistance ,flame resistance
Colour:grey(RAL7001)
Technical data:
Rated voltage:300/500V
Test voltage:2500V
Minimum bending radius:0.3m
IEC60332-1.1 993 test passed
Used under the nomal conditions.the temperature of conductor is lower than 70¡ãC
Temperature range:-15¡ãC to +70¡ãC
TVVB (Parallel) free suspension length must not exceed 35 meters,and the lift speed 1.6m/s.
TVVB(interwist) free suspension length must not exceed 80 meters, and the life speed must not exceed 4m/s.C
FLAT ELEVATOR CABLE
Properties:
The outer sheath is extensively resistant to oil and cooling liquid.
Standards:GB5023.6,IEC60227-6,EN 50214
Structure:
Conductor: fine strands of bare copper wire
Acc.to VDE0295 CLASS5
Insulation:special PVC
Colour:yellow,white,orangeg with black number with white digital coding
Bearing:steel rope
Outer sheath:flexible PVC,cold resistance ,flame resistance
Colour:grey(RAL7001).
Technical data:
Rated voltage:300/500V
Test voltage:2500V
Minimum bending radius:0.3m
IEC60332-1.1 993 test passed
Used under the nomal conditions.the temperature of conductor is lower than 70¡ãC
Temperature range:-15¡ãC to +70¡ãC
TVVB (Parallel) free suspension length must not exceed 35 meters,and the lift speed 1.6m/s.
TVVB(interwist) free suspension length must not exceed 80 meters, and the life speed must not exceed 4m/s.C.