Features: Suitable for HVAC application. Simple appearance. Multi-measurement.
Sensor type: CO2 NDIR sensor / Temp. & humidity MEMS sensor
Measuring range: 0 ... 2000 PPM / 0 ... 50 C / 0 ... 100%RH(Non-condensing)
Output: 0 ... 10 V / 4 ... 20 mA
Accuracy: 40 PPM 3% of reading / 0.5 C / 5 RH
IP rating: IP20


Display readout: 3 Digits(-199 ... +999)
Input: Current / Voltage
Output: Analog / Relay / RS-485
Accuracy: 0.2%F.S.1 digital
IP rating: IP20


Input: 4 ... 20 mA / 0 ... 10 V
Output(Isol.GND): 4 ... 20 mA / 0 ... 10 V
Accuracy: 0.1% F.S.
IP rating: IP54


Features: Designed for industrial application. Explosion proof.
Sensor type: Capacitive Humidity Sensor & Pt 100
Measuring range: Temperature -20 .+80C / Humidity 0 ... 100%RH
Output: 4 ... 20 mA
Accuracy: Temperature 0.3 C / Humidity 2%RH
IP rating: IP66


Features: Economic model for HVAC application.
Sensor type: MEMS
Measuring range: Temperature 0 .50 C / Humidity 0 ... 100%RH
Output: 4 ... 20 mA / 0 ... 10 V
Accuracy: Temperature 0.5 C / Humidity 3%RH
IP rating: IP54


Features: Suitable for small-sized device or equipment. Compact size. Various installation method.
Sensor type: Capacitive Humidity Sensor & Pt 100
Measuring range: Temperature 0 ... 100 C / Humidity 0 ... 100%RH
Output: 4 ... 20 mA / 0 ... 10 V / RS-485
Accuracy: Temperature 0.2 C / Humidity 2%RH
IP rating: IP65


Features: Suitable for clean air. Resistant to high pressure and high temperature.
Sensor type: Thermal mass flow sensor
Measuring range: 0 ... 90 m/s
Output: 0 ... 20 mA / 4 ... 20 mA / 0 ... 1 V / 0 ... 5 V / 0 ... 10 V
Accuracy: 1.5% F.S.
IP rating: IP67


Features : Designed for laminar/overflow monitoring in cleanrooms and pharmaceutical facilities.
Sensor type : Hot-wire sensor
Turndown ratio : 100 : 1
Measuring range : (0.00 ... 1 m/s), (0.00 ... 2 m/s), (0.00 ... 10 m/s)
Output : 4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Accuracy : 0.05 ... 1.00 m/s(1% of mv+0.05 m/s), 0.05 ... 2.00 m/s(1% of mv+0.1 m/s), 0.1 ... 10.00m/s(1% of mv+0.2 m/s)
IP rating : IP65

Features
Based on the hot-wire principle, featuring bi-directional measurement.
High sensitivity for low airflow, dual temperature sensors, ideal for laminar flow / overflow.
2" LCD color screen with easy settings via buttons.
The screen displays airflow and air velocity, integrated with UI settings.
Accuracy : 1.0%, operating pressure 16 bar
Multiple Outputs: Analog output / Relay / RS-485

Applications
Overflow Flow Monitoring ( 0.20 m/s) / Laminar Flow Monitoring ( 0.20 ... 0.50 m/s) / Semiconductor / Pharmaceutical / Food and Beverage / Laminar Flow Control / Overflow Control / Positive and Negative Pressure Control / Energy / Environmental Protection / Factory Automation / Pharmaceutical
*Recommended range : 0.00 ... 1.00 m/s for laminar and overflow monitoring.


Features : 2" LCD display for air/liquid flow transmitters with RS-485 and relay output, for both instantaneous and cumulative flow monitoring
Display readout : Instantaneous flow : 5-digit / Cumulative flow : 8-digit
Input : Current / Voltage / Frequency / Pulse
Output : Current / Voltage / Relay / RS-485
Accuracy : �±0.1% F.S. �±1 digit
IP rating : IP65 (Front panel)

Features
â?? High accuracy �±0.1% F.S. �±1 digit
â?? 2" LCD display, Instantaneous flow : 5-digit, Cumulative flow : 8-digit, decimal point configurable.
â?? Input signals: Current / Voltage / Frequency / Pulse
â?? Output signals: Current / Voltage / Relay / RS-485
â?? Power supply: AC 90 ... 250 V / DC 24 V
â?? Auxiliary power: DC 18 ... 26 V / 50 mA
â?? Square root function for analog signals
â?? Relay output can be configured for corresponding action modes (Hi / Lo), hysteresis, delay time, and reset delay.
â?? The linear interpolation function enables the adjustment of non-linear analog input.

Applications
Industrial / Factory Automation / Chemical Engineering / Water Treatment / Energy / Environmental Monitoring / Environmental Monitoring / Pharmaceuticals


Display readout: 5 digits(-9.9.9.9 +9.9.9.9.9)
Input: Current / Voltage
Output: Analog / Relay / RS-485
Accuracy: 0.1%F.S. 1 digital
IP rating: IP65(Front panel)


Features : Designed for industrial application. Resistant to high temperature and high pressure.
Sensor type : Capacitive Humidity Sensor & Pt 100 A class
Measuring range : 0 +180
Output : 0 ... 20 mA / 4 ... 20 mA / 0 ... 10 V
Accuracy : Temperature 0.15 C / Humidity 2%RH
IP rating : IP65


Features: Adopting the differential pressure principle for air flow measurement, enable bi-direction air flow measurement, Calculate medium density and mass flow rate
Sensor type: Differential pressure sensor
Measuring range: Standard version : (0.8 ... 40 m/s) / High-pressure version : (10 ... 200 m/s)
Output: 4 ... 20 mA + RS-485 / 0 ... 10 V + RS-485 / Frequency ( 0 ... 100 Hz ) + RS-485 / Pulse ( Option ) + RS-485
Accuracy: 1.5% F.S. (Option1% F.S.)
IP rating: IP65 (Body) / IP20 (Probe head)


Features: Suitable for compressed dry air system and industrial drying system. Integrated LED display. Faster response to low dew point.
Sensor type: Capacitive humidity sensor & Pt100
Operating range of dew point: -40 ... +60 dp C
Output: RS-485+(4 ... 20 mA / 0 ... 10 V)
Accuracy: 1 ... 1.5 dpC
IP rating: IP65(Housing) / IP20(Filter)


Features: Suitable for industrial application. Wide measuring range.
Sensor type: Piezoelectric differential pressure module
Measuring range: 50 ... 10000 pa
Output: 4 ... 20 mA / 0 ... 10 V
Accuracy: 2.0% F.S.
IP rating: IP65


Display readout: -1999 . +9999
Input: DC 4 .. 20 mA Temperature / Pressure / Level
Output: 4 ... 20 mA
Accuracy: 0.2% F.S.
IP rating: IP67


Features: Suitable for industrial application. Integrated design combines PT100 and transmitter. Easy installation.
Sensor type: RTD Pt100
Measuring range: -50 ... 200 C
Output: DC 4 ... 20 mA(2-wire)
Accuracy: 0.5% F.S.
IP rating: IP65


Sensor type : Hot-wire sensor
Turndown ratio : 100 : 1
Output : 4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Accuracy : 0.5 ... 60 m/s±(1.5% of mv + 0.8 m/s)
IP rating : IP65

Features
High Sensitivity, Low Pressure Loss, Detects Minute Airflow Changes
No Compensation Needed, Direct Flow Output
Sizes 2~12, Easy Installation
±1.5% F.S. Accuracy, 16 bar Pressure Resistance
Analog, Relay, RS-485 Outputs
Suitable for various types of gases (N2, Ar, CO2, etc.)

Applications
Compressed Air System Management / Optimization of Air Compressors & Pneumatic Equipment Efficiency / Air Dryer Flow Control / Process Gas Consumption Monitoring (N2, Ar, CO2, etc.) / Pipeline Leak Detection & Alerts / HVAC Duct Monitoring / Smart Manufacturing Energy Management / Cleanroom Airflow Monitoring / Biotech & Pharmaceutical Gas Supply Stability Monitoring / Food Processing Gas Filling & Packaging Monitoring


Features : Venturi inline type air flow measurement, a wide range of applications
Sensor type : Differential pressure sensor
Air flow measuring range : Reference airflow range table based on environmental conditions
Output signal: 4 ... 20 mA
Accuracy : ±2%
IP rating : IP65 (Housing)

Features
Precision measurement : Adopting the unique fluid dynamics principles of Venturi tube, the FDM08 provides accurate measurement.
Wide range of applications : Suitable for general gases, steam, contaminated gases, or high-humidity gases.
Stable performance : No moving or electronic parts inside the pipeline, ensuring excellent long-term stability.
Easy installation : Shorter front and rear straight pipe sections compared to standard throttling devices, approximately 2.5D in the front and 2D in the rear.
Low pressure loss : Designed to minimize pressure loss, reducing energy consumption.

Applications
Compressed air systems / Boiler systems / Industrial process gases / Water treatment aeration systems


Feature : Utilizing hot-wire sensing technology, high sensitivity for detecting minute differential pressure
Measuring element : Thermal mass type
Measuring range : ±25, ±50, ±100 Pa
Output : 4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Accuracy : ±(1% F.S. + 0.1 Pa)
IP rating : IP65

Features
Thermal mass sensing for differential pressure
High sensitivity at low pressure, low zero drift, range ±25, ±50, ±100 Pa
Supports square root function for analog output
2 LCD with easy button setup
Analog output with RS-485 / Relay
Compact metal housing, easy to install
Resolution up to 0.05

Applications
Industrial / Agricultural / Ceramics & Glass / Chemical / Transportation / Technology / Energy / Environmental / Factory Automation / Pharmaceutical / Food & Beverage


Features: Multi-point averaging. Suitable for large pipe. Resistant to high temperature, and corrosion.
Operating pressure: Max.10 bar
Operating temperature: Max.250 C
Length: 4.. 40"(100 ... 1000 mm)


Features: Designed for industrial application. Resistant to high temperature and high pressure.
Sensor type: Capacitive Humidity Sensor & Pt 100 A class
Measuring range: 0 . +180C
Output: 0 . 20 mA / 4 . 20 mA / 0 ... 10 V
Accuracy: Temperature 0.15 C / Humidity 2%RH
IP rating: IP65


Features : Multi-point averaging. Suitable for large pipes. Resistant to high temperature and corrosion.
Operating pressure : Standard type : Max. 10 bar / High-temp. type : Max. 4 bar
Operating temperature : Standard type : Max. 200�°C / High-temp. type : Max. 600�°C
Length : 12"(300 mm)

Features
â?? Pitot tube : Measure differential pressure caused by flow, combined with differential pressure sensor to calculate flow.
â?? Multi-Hole Structure : Averages differential pressure readings from multiple points for stable and reliable measurements.
â?? High Sensitivity : Low pressure drop within the tube enables measurement of small value, with sensitivity down to 1 Pa.
â?? Durable Material : Made of SS316, providing strong corrosion resistance and long-term stability across diverse environments.
â?? Environment Resistant : Ideal for extreme conditions. Options for operating temperature up to 600C and pressure up to 10 bar.
â?? Dust-Resistant : Features a dust-resistant structure that resists clogging, ensuring stable flow measurement.

AFMP adapts the Pitot tube principle, where the combination of the Pitot tube and a differential pressure sensor is commonly used for flow measurement. It measures the differential pressure between the total pressure and static pressure of the fluid, allowing for the calculation of fluid velocity. The difference between total and static pressure is known as dynamic pressure, which results from fluid flow and is proportional to the square of the flow velocity. By measuring dynamic pressure, the fluid speed can be accurately determined.
The AFMP averaging Pitot tube features a multi-hole structure, which averages pressures from multiple points to better represent the actual flow profile within the pipe, ensuring stable and precise measurements.

Applications
HVAC system / Ventilation ducts / Exhaust gas treatment / Low and high flow measurement


Features : Utilizes a unique Venturi tube structure, the Inline type air flow sensor designed for compressed air system
Sensor type : Hot-wire sensor
Turndown ratio : 100 : 1
Measuring range : 0 ... 4000 m�³/h
Output : 4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Accuracy : �±1.5% F.S.
IP rating : IP65

Features
â?? Precise Measurement : Utilizes a unique Venturi tube structure
â?? 2â?³ LCD Screen : Easily configurable with buttons
â?? Display Features : Shows instant and cumulative measurements; screen rotates 90 degrees for easy viewing
â?? Multiple Pipe Diameters Available : (DN15 / DN25 / DN40 / DN50 / DN80 / DN100) for easy installation
â?? Accuracy : �±1.5% F.S., pipeline withstand pressure of 16 bar
â?? Multiple Outputs: Analog output / Relay / RS-485

Applications
Compressed Air Systems / Pneumatic Systems / Dryers / Air Consumption Monitoring / Pipeline Leak Monitoring


 
 
Contact Supplier