Key specifications/special features for surge arrester:
System nominal voltage(kv): 33
Type code of moa: yh10w-30/90
System highest voltage(kv): 36
Rated voltage of arresters(ur)(kv): 30
Continuous operationg voltage(ur)(kv): 24
Nominal discharge current(in)(kv): 10
High current 4/10 impulse withstand(ka): 100
2ms rectangular current(a): 250
Steep current impulse residual voltage(kv): 99
Lightning impulse residual voltage(kv)
5ka: 85
10ka: 90
20ka: 101
Switching current impulse residual voltage(kv): 69
Lind discharge class: i
Pressure relief class: b, 20
Insulation impulse withstand voltage(kv): 170
Power frequency withstand voltage(kv): 95
Max. External riv(v): <=500
Max. Partial discharge(pc): <=10
Creepage distance(mm): 1007
Note: if arrester with porcelain housing, type code should not include"h". We can produce both in porcelain housing and polymeric housing.
3 pcs a carton
Technical parameters for XRNT-36KV fuse:
Rated voltage: 36KV
Rated current of fuse: 25A
Dimension: 442mm*51mm
Type Rated voltage (KV) Rated current (A) Diameter (mm) Length (mm)
XRNT1 3.6 6.3 10 16 20 25 31.5 40 51 192
XRNT1 7.2 6.3 10 16 20 25 31.5 40 50 63 51 292
XRNT1 7.2 80 100 125 160 76 292
XRNT1 12 10 16 20 25 31.5 40 51 292
XRNT1 12 50 63 71 80 100 76 292
XRNT1 12 125 76 292
XRNT1 12 160 200 88 292
XRNT1 24 6.3 10 16 20 25 31.5 40 51 442
XRNT1 24 50 63 71 80 100 76 442
XRNT1 24 125 76 442
XRNT1 24 160 88 442
XRNT1 40.5 3.15 6.3 10 16 20 25 51 537
XRNT1 40.5 31.5 40 76 537
XRNT1 40.5 63 88 537
3pcs a carton
Din hrc "s" type high voltage fuse for transformer protection:
1. According to bussmann din "s" type high performance back-up fuse
2. Comply with iec282-1, din, bs
3. This fuse is intended to protect distribution networks and transformer, for indoor as well as outdoor use.
4. Any other specifications can be designed specially.
Type rated voltage (kv) rated current (a) diameter (mm) length (mm)
Xrnt1 3.6 6.3 10 16 20 25 31.5 40 51 192
Xrnt1 7.2 6.3 10 16 20 25 31.5 40 50 63 51 292
Xrnt1 7.2 80 100 125 160 76 292
Xrnt1 12 10 16 20 25 31.5 40 51 292
Xrnt1 12 50 63 71 80 100 76 292
Xrnt1 12 125 76 292
Xrnt1 12 160 200 88 292
Xrnt1 24 6.3 10 16 20 25 31.5 40 51 442
Xrnt1 24 50 63 71 80 100 76 442
Xrnt1 24 125 76 442
Xrnt1 24 160 88 442
Xrnt1 40.5 3.15 6.3 10 16 20 25 51 537
Xrnt1 40.5 31.5 40 76 537
Xrnt1 40.5 63 88 537
3pcs a carton
Type k high voltage fuse link for dropout fuse cutout.
1). Product description:
This fuse wires apply to the 11kv -36kv drop out fuse.
2). Standard:
According to ansi/ieee c37.41-2000 and iec-282 standard.
3). Technical specification:
Rated current: 1a-300a
Rated voltage: 11kv-27kv
Length: 530mm-600mm (23 inch)
Length of fuse link can be make according to requests.
500pcs a carton
Advantages:
1. Full scope protection
2. High breaking capability
3. High voltage current limiting fuse
4. Design as customer required
5. Utility model patent
6. Appearance design patent
Specification:
Material: ceramic
Color: white, brown
Length: 142mm, 192mm, 195mm, 260mm, 355mm, 465mm
Diameter: 22mm, 25mm, 51mm
Type rated voltage (kv) rated current (a) diameter (mm) length (mm)
Xrnp1 3.6 0.5 1 2 3.15 6.3 22 25 142
Xrnp1 7.2 0.5 1 2 3.15 6.3 22 25 142
Xrnp1 7.2 0.5 1 2 3.15 6.3 22 25 192 195
Xrnp1 10(12) 0.5 1 2 3.15 22 25 192 195
Xrnp1 24 0.5 1 2 3.15 22 25 355
Xrnp1 24 0.5 1 2 3.15 30 365
Xrnp1 40.5 0.5 1 2 3.15 30 465
3 pcs a carton