CT-TSS2000 Time Synchronization System
CT-TSS2000 Time Synchronization System consists of CT-TSS2000 Grandmaster and CT-KZ001 Time Code distributor. Each grandmaster receives GPS or BD as well as external IRIG-B time signal. While the optional CT-KZ001 time code distributors are synchronized by a CT-TSS2000 Grandmaster. The whole system supports multi-format outputs, can meet the demands of various industrial users, is a stable and reliable time synchronization system widely used in power , telecom networks, railways and other fields etc.
Functions
Multiple time signal input: BD B1, GPS L1, IRIG-B code
Multi-format outputs: NTP, SNTP, IRIG-B, Serial and Pulse
1x 10/100 Base-T Ethernet interface for management
Internal precision time-keeping via high precision oscillator
Support IEC61850, IEC60870-5-104 standard
Fault alarm functions for time source, board cards, power supply and so on.
Grid frequency measurement function is optional
Time delay compensation mechanism, compensation range: 20ns~500ms
Time continuity judgment mechanism to avoid output time discontinuity
Features
Support multiple time sources selection
Flexible module card design, easy for outputs configuration
Support duplex, hot standby, cold standby configuration
LCD display with man-machine interaction brings a simple operation
Adapt to the strong electromagnetic interference environments
Redundant Dual power supplies
19’’ / 3U rack mount
Specifications - Grandmaster
Time Reference: BD B1, GPS L1,IRIG-B
Outputs: IRIG-B TTL?RS422/RS485?RS232?fiber?idle contact
Pulse (1PPS, 1ppm, 1PPH) TTL?RS422/RS485?RS232?fiber?idle contact
NTP/SNTP RJ45
Serial(TOD) RS232
Network management RJ45
Time Performance:
Time Accuracy to UTC =1µs(RMS)
Holdover Accuracy =55µs /hr (Lose of GPS after 12hours)
Network Services:
Network Interface 10 / 100M RJ45 Ethernet port, ST fiber port
NTP time sync accuracy 1ms ~ 10ms (depending on the network environment)
NTP access ability 2000 requests per second
Protocols RFC-1059(NTP v1),RFC-1119(NTP v2),RFC-1305(NTP v3),RFC-5905(NTP v4), RFC-2030(SNTP) TELNET, HTTP, (SSH,DHCP,FTP are customizable) IEC61850, IEC60870-5-104
Installation 19 "/ 3U standard chassis
Note: the CT-KZ001 Time Code Distributor receives 2 lines IRIG-B time signal from the Grandmaster as time reference, if any loss of the both 2 lines IRIG-B signal, the internal oscillator will keep working to ensure normal time output. Other detailed parameters please refer to CT-KZ001 Time Code Distributor introduction.