GF112B Single Phase kWh Meter Calibrator is suitable to test various types single phase kWh meters error on site and also can be used to test alternating current parameters - U, I, P, Q, S ,F, E etc.
INTRODUCTION
GF112B Single-Phase kWh Meter Calibrator is suitable to test various types single phase meters on site and also can be used to test alternating current parameters.
TECHINICAL SPECIFICATION
Electrical parameter
Accuracy class 0.2%
Active power measurement accuracy 0.2%, 0.5%
Energy measurement accuracy 0.2%, 0.5%
Power supply AAA type, Li rechargeable battery, 750mAh, 3.6V
it can work 8 hours continuously
Warming-up time
DDS5558 Single Phase Meter is a kind of new style single phase two wire active energy meter, it adopts micro-electronics technique, and imported large scale integrate circuit, use advanced technique of digital and SMT techniques, etc. It has minimum size, and also a new single phase two wire active energy meter. It has already passed the test of the international authority CE.
The meter completely accords with relevant technical requirements of class 1 single phase active energy meter stipulated in international standard IEC 62053-21. It can accurately and directly measure 50Hz or 60Hz active energy consumption from single phase AC electricity net. This meter has white backlight source eight digits LCD monitors shows the active energy power consumption. It has following features: Good reliability, small volume, light weight, specious nice appearance, convenient installation, etc.
Features:
Bi-directional total active energy measurement
25mm standard DIN rail installation, complying with standard DIN En50022.
Single pole width (Modules17.5mm), complying with standard DIN43880.
Small modular size, DIN rail mounted.
Easy installation to distribution boards, load center, miniature & etc. by identifying where energy is being used.
Application:
All power parameter measurements;
Energy measurement and electrical fire monitor and control;
Replacing the three-phase power meter, three-phase electricity transmitter;
Transformers, generators, capacitors, and electric motors distributed detection;
Medium and low-pressure systems;
SCADA, EMS, DCS integrators.
6807 Single Phase Energy Meter Calibrator Suppliers
Short on time? Let Single Phase Energy Meter Calibrator sellers contact you.
GF312V2 portable three phase multifunction watt-hour meter calibrator on-site is the newest product produced by our company by widely visiting users and referring to the advantages of the same kind of products home and abroad. The measured part of the product adopts high speed A/D transmission to send DSP to conduct digital processing, which largely improves measured degree of accuracy and stability. Central processing part adopts 32-bit ARM embedded technology to make instrument interface novel, function abundant, operation distinct and easy, and performance steady. Class of accuracy: Class 0.02, 0.05 or 0.1, range from 12A/600V or 120A/600V, with comfort design, small size and light weight. The model GF312V2 watt-hour meter calibrator is suit for electric power departments, measuring and quality examining departments and electric lab to field use.
GF312B portable three phase energy meter calibrator with printer is used to calibrate three phase, single phase, active and reactive energy meters error. And it also can be used as voltage, current and power meter to measure AC parameters of three phase power line. It can measure wave distortion factor and 2nd to 64nd harmonic wave. GF312B calibrator is used for grid corporation of measurement and energy test center, metrological service of power supply bureau, national energy measurement of testing authorities.
The instrument GF312D1 is a precision 0.05% AC energy meter testing instrument, mainly used to test three phase energy meter error on site, measure all various of AC parameters and CT ratio & phase error, it is also as three phase reference energy meter in the laboratory. Mainly using test single phase or three phase meter error on site. GF312D1 energy meter calibrator is an ideal test tool for the metrological service of electricity power company.
Three Phase Energy Meter Field Calibrator is a precision AC energy meter testing instrument, mainly used to test three phase energy meter error on site and measure various of AC parameters.
INTRODUCTION
The GF302D1 three phase portable energy meter test system consists of an integrated three phase current and voltage source(up to 500V/120A or 500V/20A) and built-in three-phase electronic reference standard of accuracy class 0.05%. Characteristic features of the GF302D1 are its wide measuring range, high accuracy and high tolerance to unwanted external influences. The equipment offers high functionality combined with an excellent menu guided operation via built-in keyboards and colored 7 touch LCD-display.
PARAMETERS
Accuracy class 0.05%, 0.1%
Power supply One Phase AC 100-265V, frequency 50/60Hz.
AC Voltage output
Range(U1,U2,U3) 57.7V, 100V, 220V, 380V
or 69.3V, 120V, 240V, 480V( optional)
Adjustment range (0-120)%RG(1)
Adjust fineness 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability 0.01%/120s
Distortion 0.3% (Non-capacitive load)
Output load each phase 30VA
Measuring accuracy 0.05%RG
AC Current output
Range (I1, I2, I3 ) 200mA, 1A, 5A, 20A, 100A(optional)
Adjustment range (0-120)%RG
Adjustment fineness 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability
INTRODUCTION:
The instrument is a precision AC energy meter testing instrument, mainly used to test three phase energy meter error on site and measure all various of AC parameters.
FEATURES
Three phase active or reactive electricity energy meter.
Calibrate three phase, single phase, and active or reactive meter error.
Measure U(voltage) of three phase or single phase.
Measure I(current) of three phase or single phase.
Measure active power of three phase or single phase.
Measure reactive power of three phase or single phase.
Measure apparent power of three phase or single phase.
Measure power factor of three phase or single phase.
Measure phase angle between voltage and current.
Measure frequency of power line.
Display vector diagram.
Display waveform of U and I.
Analyze and display content of harmonic of U and I.
Measure 2-64 harmonic of U, I.
Store and display measured data.
Optional 5A, 20A, 100A, 500A, 1000A, 2000A, 3000A current clamp.
Measure CT variable ratio.
Measure the ratio or lag-angle of low-voltage transformer.
Adopt 32 bit ARM processor, multi-channel 16 bit precision A/D convertor, high resolution TFT color LCD.
Inner equipped with 0.01% wide-range current transformer and can be equipped with various type current clamps, wide range of measurement and high veracity.
Low consumption circuit design, high energy Lithium battery supply, intellectual power management software, which enables the instrument continuously working up to 10 hours.
The Portable Three Phase kWh Meter test equipment is used for grid corporation of measurement and energy test center, management department of power supply bureau, national energy measurement of testing authorities, and also used to test each kind of single/three phase kWh meter of industries and mining enterprises as well as electric meter manufacturers. Meanwhile, the calibrator also can be used as one high precision standard power source.
This type of single-phase electronic multi-tariff prepayment energy meter is an active meter with the data exchange method of numeric medium. The user can load the amount which purchase in advance, make the statement by amount. This meter was equipped with numeric keyboard interface used to active energy metering and prepayment control. Besides, this meter also have infrared communication, RS485 or RS232 communication, metering components, real-time-clock device, load controlling switch and other auxiliary equipment.
Single Phase DIN-Rail Energy Meter (DDS-1Y-L)
Executive Standard: IEC62052-11 2003; IEC62053-21 2003 and IEC62056-21(IEC1107)
DIN-rail standard: "SO"43864.
Function and characteristic:
Single measurement(optional RS485 or RS485 Modbus)
High accuracy of measure, convenient installation;
Logical design of Anti-creep.
Technical data:
Rated voltage: 110V, 120V, 220V, 230V
Rated Current: 1.5(6)A, 5(60)A, 10(100)A
Frequency: 50-60Hz
Connection mode: CT type; Direct type
Display mode: LCD 5+2 = 99999.99kWh
Accuracy Class: 1.0
Power consumption: 1W (when 220V 20A)
Start current: 0.004Ib
Constant: 12800 imp/kWh; 800/1600/3200/6400 imp/kWh
Standard work temperature: -20-45 degree
Climate work temperature: -30-55 degree
Relative humidity: 85%.
Major technical data:
Name of product: single phase long life electronic energy meters
Type: dds 318
Accuracy class: 1.0
Power consumption :< 6va
Rated voltage: 220v 240v
Rated current: 2.5(10) a 5(30) a 10(50) a
Application:
By adopting advanced pcb and smt technology, dds318 single phase long life electronic energy meter is used to measure the energy of 50hz single phase a.C power.
Salient feature:
1.High accuracy:1.0class
2.High overload capacity: 6 times of overload.
3.High reliability: long operating life.
4.Low power consumption, small size, light weight, tamper proof and easy to install.
5.Smt and re-flow soldering technology is adopted. Meter has strong capability for disturbance. Emc can comply with requirement of iec61036-2000.
6.With impulse output interface for direct calibration of the meterf+s accuracy, or for measurement of the impulse input in case of mass-metering.
7.Power indicator to test the optical power end and calibrate the accuracy of the meter.
8.Electric power line carrier system and telephone remote-metering system can be supplied for userf+s option.
9.It can be changed into single phase plc electronic energy meter
Features:
1) high accuracy, reliability, overload capability
2) low power consumption
3) smt technology and re-flow soldering technology
Major technical data:
1) accuracy class: 1.0
2) power consumption: less than 4va
3) rated voltage: 200v
4) rate current: 2.5(10)a, 5(25)a, 10(40)a
Main functions:
1) measurement of single-phase 50hz active power and power consumed
2) set up maximum load, overload warning and power off
3) warning of remained energy and remind user for payment
4) re-read power consumed, remained energy and number of prepayments for power
5) power off when no energy in the meter
6) parameter transferring through ic card
Salient features:
1) high accuracy: 1.0 class
2) high overload: 6 times of overload
3) high reliability: long operating life
4) low power consumption, tamper-proof, light weight, small size and easy to install
5) register displays consumed power, and led displays status of consumed power
6) smt technology and re-flow soldering technology are adopted. Meter has strong
Capability for disturbance. Emc can comply with requirement of iec 61036-2000
High overload capacity, high reliability of relay
Single-phase and 3-phase pre-payment electronic energy meters can share one set
Light weight, small size, easy to install
DESCRIPTION
The DDSY1088 single phase two wire postpaid meter is made of high quality optimized long life components and designed in advanced SMT technique with good performances on reliability, accuracy and load ranges.DDSY1088 provides metering solution benefiting both consumers and power utilities. It complies with the applicable standards of IEC1036, IEC62052-11, IEC62053-21.
FEATURES
1. High accuracy measurement with LCD display,5 integers.
2. Wide operating voltage range 0.8Un ~ 1.15Un.
3. Long time precisely works without calibration and limit error linear maintains flat during heavy loading from start to end.
4. With active impulse LED indicator and reverse energy LED indicator
5. With cover of terminal block made by transparent material.
6. Measures active energy,reactive energy and reverse always add to positive.
7. Meter base and cover ultrasonic sealed
The single phase two wire electronic meter is made of high quality optimized long life components and designed in advanced SMT technique with good performances on reliability, accuracy and load ranges.
featured with source-load missing neutral anti-tamper function, and provides metering solution benefiting both consumers and power utilities.
It complies with the applicable standards of IEC1036, IEC62052-11, IEC62053-21.
FEATURES
1. LCD display with backlight function even if power failure.
2.Wide operating voltage range0.7Un ~ 1.15Un, withstand 1 hour limit operating voltage up to 380V.
3.The meter can works under harsh environment conditions of kind of variations by high accuracy in a long time
4.without calibration, and its limit error linear maintains flat even during heavy loading status from start to end.
5.Useful infrared communication for meter reading and setting.
6.With active impulse LED indicator and impulse test output.
Anti-Tamper function.
7.Measures voltage and current with LCD display.
8.Maximum demand.
6807 Single Phase Energy Meter Calibrator Suppliers