Transformer Standard current transformer are also called precision current transformers, current transformer standards, standard CT and current transformer standards. Transformer standards are divided into current transformer standards and voltage transformer standards. Standard current transformers are used in the error test of transformers. Used as a current transformer calibration standard
technical parameter
1. Temperature:
2. Relative humidity
3. Rated Primary Current:5-5000A 5A,1A
4.Rated secondary current:5 1A
5 Accuracy Class 0.05S
6. Allow long-term work under the rated current; More than120A across the core.
Precautions:
1. The current of standard CT and tested CT must be the same in CT calibration.
2. Follow the given wiring diagram strictly.
3. Test whether the load box is accurate or not before calibrating the transformer.
4. Forbid secondary winding opening during the calibration.
5. Select demagnetization before calibration.The wiring diagram is shown in figure 5.
Short out the secondary winding before cutting off the power when the demagnetization is finished.
6.Principle wiring diagram of CT with large current generator is similar to above diagram. They are the same except the output winding of large current generator and primary winding of transformer are the same one.
Transformer Standard current transformer are also called precision current transformers, current transformer standards, standard CT and current transformer standards. Transformer standards are divided into current transformer standards and voltage transformer standards. Standard current transformers are used in the error test of transformers. Used as a current transformer calibration standard
technical parameter
Temperature -5 40
Relative humidity 80%
Rated Primary Current 5-5000A 5A,1A
Rated secondary current 5A 1A
Accuracy Class 0.05S
Allow long-term work under the rated current; More than120A across the core.
Precautions
The current of standard CT and tested CT must be the same in CT calibration.
Follow the given wiring diagram strictly.
Test whether the load box is accurate or not before calibrating the transformer.
Forbid secondary winding opening during the calibration.
Select demagnetization before calibration.The wiring diagram is shown in figure 5.
Short out the secondary winding before cutting off the power when the demagnetization is finished.
Principle wiring diagram of CT with large current generator is similar to above diagram. They are the same except the output winding of large current generator and primary winding of transformer are the same one.
Transformer dc resistance test instrument is an indispensable test project of Transformer after handing in pick up overhaul and change sub-pick up switch. In general using traditional methods (bridge method and pressure drop method) measurement transformer winding group and dc resistance of large power inductance equipment is a time-consuming and time-consuming work. In order to change this situation shorten measurement time and reduce the work burden of test personnel huatian electric power company developed Transformer dc resistance test instrument (hereinafter referred to as direct resistance instrument). It adopts new power supply technology featuring stable performance rapid measurement small volume easy to use high measurement precision and good data repeatability. Measurement transformer around the group and large power inductor dc resistance ideal equipment.
product namesï¼?Dc resistance tachometerã?? Transformer dc resistance test instrumentã?? Transformer winding dc resistance test instrument Transformer direct resistance speed meter Transformer direct resistance quick test instrument Inductive load Dc resistance tachometer Inductive load dc resistance rapid test instrument Inductive load dc resistance test instrument
Product Introduction
TKJB - 1200 Six phase voltage and six phase current can be output, which has made it is possiable to be any combition, such as the output mode of the combination of conventional four phase current and three-phase current, six phase voltage mode, six phase current mode and 12 phase output mode. It not only can be compatible with the traditional way of various tests, but also can conveniently carry out differential test of three-phase transformer
Product Characteristics
1 Meet all field test requirements.The Microcomputer relay protection tester is a standard of six phase current six phase voltage output at the same time the current a/phase 30 voltage125V/phase.Six - phase current in parallel up to 180A.It can not only test the traditional relays and protection devices but also test the modern microcomputer protection especially the transformer differential protection and backup self-switching device the test is more convenient and perfect.
2 All kinds of technical indexes have reached the standard of DL/ t624-1997 "technical conditions of microcomputer test equipment for relay protection" issued by the ministry of electric power.
3 Classic WindowsXP operation interface man-machine interface friendly easy and quick to operate;The high-performance embedded industrial control computer and 8.4-inch TFT true-color display with a resolution of 800-600 provide rich and intuitive information including the current working status of the device and various help information.
4 The native Windows XP system with recovery function to avoid illegal shutdown or misoperation caused by the system crash.
5 The device has an ultra-thin industrial The keyboard and a photoelectric mouse that handles everything just like a PC.
6 The main control board adopts DSP+FPGA structure and 16-bit DAC output which can generate high-density sinusoidal wave of 2000 points per week for the basic wave greatly improving the quality of waveform and improving the precision of tester.
7 High-fidelity linear power amplifier ensures the accuracy of small current and the stability of large current.
8 The Microcomputer relay protection tester with USB interface and PC communication directly without any connection easy to use.
9 Connect to laptop (optional) to run.Laptop computer and industrial computer use the same set of software no need to learn how to operate.
10 It is equipped with the independent auxiliary voltage source output the output voltage is 110V(1A) and 220V(0.6a) respectively.To be used by relays or protective devices that require dc working power.
11 With the function of software self-calibration it avoids the need to open
146 Turbines Generator Transformers Tg Auxiliaries Non Destructi Suppliers
Short on time? Let Turbines Generator Transformers Tg Auxiliaries Non Destructi sellers contact you.
Transformer winding deformation test instrument based on the measurement of the characteristic parameters of transformer internal winding the internal fault frequency response analysis (FRA) method which is being developed in developed countries is adopted to make an accurate judgment of transformer internal fault.
After the design and manufacture of transformer is completed the line coil and internal structure are determined. Therefore for a multi-winding transformer line coil if the voltage grade is the same and the winding method is the same the corresponding parameters (Ci Li) of each line coil should be determined. Therefore the frequency domain characteristic response of each line coil is determined accordingly and the frequency spectrum of the corresponding three-phase line coil is comparable to some extent.
The distribution parameters of transformer windings will change when short-circuit between turns and phases occurs in the test process or collision occurs in the transportation process resulting in the relative displacement of the line coil and the deformation of the line coil caused by electromagnetic tension in the short-circuit and fault state during the operation process. Then it influences and changes the original frequency domain characteristics of the transformer that is amplitude change of frequency response and resonance frequency offset. The transformer winding test instrument developed according to the response analysis method is such a novel non-destructive testing equipment for transformer internal faults. It is suitable for the internal structure fault detection of 63kV ~ 500kV power transformer.
product names Electric power transformer winding deformation test instrument Transformer winding deformation detector Transformer winding deformation meterTransformer winding deformation analyzer
High-speed transformer verification device is a new generation of transformer verification device developed by our company. The design idea of virtual instrument is adopted. The user only needs to operate the virtual instrument interface on the computer screen through the mouse and keyboard to input the transformer type range accuracy level capacity power factor and other parameters can complete automatic testing of current transformers and voltage transformers as well as analysis calculation and database management of test results and can be printed according to user needs various records and certificates.
1. The automatic mutual-inductor calibration platform adopts a single chip microcomputer to realize the functions of measurement control and display.
2. With computer interface improve the level of office automation and reduce the labor intensity.
3. Can have a large screen display provide a friendly operation interface and rich measurement information.
4. It can automatically realize the measurement of the transformer and can automatically switch the current and voltage load box.
5. Possess good catching measures and be able to promptly inform users of wrong information.
6. This automatic transformer calibration station can reach level 2.
7. The transformation ratio of the standard transformer and the tested transformer does not have to be equal as long as the rated primary voltage or rated primary current of the standard transformer is greater than or equal to the rated value of the tested transformer it can be directly verified which is more convenient to use.
Dc resistancetest around group is an indispensable test project of transformer after the submission of pick up overhaul and change of subpick up switch. In general using traditional methods (bridge method and pressure drop method) measurement transformer winding group and dc resistance of large power inductance equipment is a time-consuming and time-consuming work. In order to change this situation shorten measurement time and reduce work burden of test personnel, our company developed Dc resistance rapid test instrument (hereinafter referred to as direct resistance instrument). It adopts new power supply technology featuring stable performance rapid measurement small size easy to use high measurement precision and good data repeatability. Measurement transformer is around the group and large power inductor dc resistance ideal equipment
product names Dc resistance tachometer Transformer dc resistance test instrument. Transformer winding dc resistance test instrument. Transformer direct resistance speed meter Transformer direct resistance quick test instrument Inductive load Dc resistance tachometer Inductive load dc resistance rapid test instrument Inductive load dc resistance test instrument Dc resistance tester
standard current transformer is used as a standard for calibrating current transformers, Used as a standard to calibrate current transformer whose accuracy class is two or more lower than itself. The grounding pole of the machine shell must be grounded. To avoid electric shock, the conductor must be connected to the ground
Technical index
1. Temperature: -5-40
2. Relative humidity: 80%
3. Allow long-term work under the rated current; More than 600A across the core.
Feature;
1. The current of standard CT and tested CT must be the same in CT calibration.
2. Follow the given wiring diagram strictly.
3. Test whether the load box is accurate or not before calibrating the transformer.
4. Forbid secondary winding opening during the calibration.
5. Select demagnetization before calibration.Short out the secondary winding before cutting off the power when the demagnetization is finished.
6.Principle wiring diagram of CT with large current generator is similar to above diagram. They are the same except the output winding of large current generator and primary winding of transformer are the same one.
40KV vlf high voltage generator of this product fully complies with the standards of the electric power industry. Mechanical methods are widely used to modulate and demodulate ultra-low frequency signals, but there is no standard sine wave, some errors in high-voltage part measurement and spark discharge. The product can overcome the above shortcomings.
How to choose the suitable products for test
Please make sure that the capacitance of test products is below the instrument rated capacitance. The waveform will be influence if the capacitance of test products is too small and the instrument can not normally output when it below 0.05�µF. 0.05�µF capacitor in parallel to auxiliary output. Below is capacitance of some instrument for your reference.
40KV vlf high voltage generator parameter :
Model
Rated Voltages
Load capacity
Fuse
Weight
Useful
VLF-40
40kV
(peak )
0.1Hz,1.1µF
20A
Control 6
Body Boost 50
Used for cable and generator with corresponding voltage
0.05Hz, 2.2µF
0.02Hz, 5.5µF
0.01Hz, 11.0 µF
Theory of Ultra-Low Frequency Dielectric Strength Test
Ultra-low frequency dielectric strength test is an alternative method of power frequency withstand voltage test.As we know, due to the large capacitance of the insulating layer, a large-capacity test transformer or resonant transformer is required to perform power frequency withstand voltage tests on large generators and cables. Huge equipment is not only cumbersome, but also expensive and unsuitable for use.
40KV vlf high voltage generator of this product fully complies with the standards of the electric power industry. Mechanical methods are widely used to modulate and demodulate ultra-low frequency signals, but there is no standard sine wave, some errors in high-voltage part measurement and spark discharge. The product can overcome the above shortcomings.
How to choose suitable products for test
Please make sure that the capacitance of test products is below the instrument rated capacitance. The waveform will be influence if the capacitance of test products is too small and the instrument can not normally output when it below 0.05 F. 0.05 F capacitor in parallel to auxiliary output. Below is the capacitance of some instruments for your reference.
40KV vlf high voltage generator parameter :
Model
Rated Voltages
Load capacity
Fuse
Weight
Useful
VLF-40
40kV
(peak )
0.1Hz, µF
20A
Control
Body Boost 50
Used for cable and generator with corresponding voltage
Impulse voltage generator is mainly used for impulse voltage test of power equipment such as lightning impulse voltage full wave lightning impulse voltage truncation wave and operating impulse voltage wave to test insulation performance.Impulse voltage generator a power supply device that imitates impulse voltages such as lightning and operating overvoltages.It is mainly used in insulation shock withstand voltage and dielectric shock breakdown and discharge tests.
Scope of application: standard lightning shock lightning cut-off wave for transformers reactors mutual transformers and other high voltage electrical appliances high voltage thyristor valve SVC(HVDC) power cables all kinds of high voltage insulators bushing operation shock and all kinds of non-standard shock wave impulse voltage test required by users.Various test waveforms (standard and non-standard waveforms user-generated waveforms) can be generated by a single set of equipment.Field of application: lightning protection and lightning test for quality inspection measurement inspection and supervision organizations power equipment manufacturers railway communications aerospace and aerospace vehicles military research units universities and meteorological departments.
900kV/67.6 kJ Lightning Impulse Voltage Generator Complete Test Equipment for Transformer Reactor Cable
Impulse voltage generator is mainly used for impulse voltage test of power equipment such as lightning impulse voltage full wave lightning impulse voltage truncation wave and operating impulse voltage wave to test insulation performance.Impulse voltage generator a power supply device that imitates impulse voltages such as lightning and operating overvoltages.It is mainly used in insulation shock withstand voltage and dielectric shock breakdown and discharge tests.
Scope of application: standard lightning shock lightning cut-off wave for transformers reactors mutual transformers and other high voltage electrical appliances high voltage thyristor valve SVC(HVDC) power cables all kinds of high voltage insulators bushing operation shock and all kinds of non-standard shock wave impulse voltage test required by users.Various test waveforms (standard and non-standard waveforms user-generated waveforms) can be generated by a single set of equipment.Field of application: lightning protection and lightning test for quality inspection measurement inspection and supervision organizations power equipment manufacturers railway communications aerospace and aerospace vehicles military research units universities and meteorological departments.
900kV/67.6 kJ Lightning Impulse Voltage Generator Complete Test Equipment for Transformer Reactor Cable
Product Description
ZGS type DC high voltage generator used AIPWM technique adjusted the inaccuracy linearity of PWM technology let the instrument precision greatly improved. It is mainly used in the electric power department power department of industrial and mining metallurgy iron and steel enterprise for zinc oxide lightning arrester power cables transformers circuit breakers generators and other high voltage electrical equipment of DC withstand voltage test or DC leakage current test.
Product Characteristics
1ã??Dc high voltage generator adopts high frequency PWM technology to make closed adjustment with high voltage stability, small ripple factor and fast reliable protection circuit. The generator can endure direct discharge by devices of large capacitance. It is of small size and of light weight, convenient for field use.
2 Full range of linear smoothly adjusted voltage, with voltage regulation accuracy smaller than 0.1%; voltage measurement accuracy is 0.5%, resolution 0.1kv; Current measurement accuracy is 0.5%, the minimum resolution: control box 1µA, shock resistance current 0.1µA.
3 The generator uses AC 220 V power supply (AC220V±10%, 50 hz±1%), the ripple factor is less than 0.5%, and can be used for all-weather at the site .
4 High voltage multiplier uses Dupont materials for full solid encapsulation, overcoming the inconvenience brought by the air and oil filled equipment. Broad base and outer cylinder of light quality makes it stand steadily and more convenient for maintenance.
5 75% MOA voltage switch button, simple and convenient testing arrester.
6 Over-voltage setting function displays the over-voltage value during regulation process; perfect protection against discharge of over-voltage, over-current and short circuit. This is the best companion for cable experiments.
7 Perfect break line and non-zero potential start protection function protects the operator and samples at any time. This product has overall design of shock-proof control box, concise, clear panel design and voice prompt for operation.
Product Description
ZGS type DC high voltage generator used AIPWM technique adjusted the inaccuracy linearity of PWM technology let the instrument precision greatly improved. It is mainly used in the electric power department power department of industrial and mining metallurgy iron and steel enterprise for zinc oxide lightning arrester power cables transformers circuit breakers generators and other high voltage electrical equipment of DC withstand voltage test or DC leakage current test.
Product Characteristics
1 Dc high voltage generator adopts high frequency PWM technology to make closed adjustment with high voltage stability, small ripple factor and fast reliable protection circuit. The generator can endure direct discharge by devices of large capacitance. It is of small size and of light weight, convenient for field use.
2 Full range of linear smoothly adjusted voltage, with voltage regulation accuracy smaller than 0.1%; voltage measurement accuracy is 0.5%, resolution 0.1kv; Current measurement accuracy is 0.5%, the minimum resolution: control box 1�µA, shock resistance current 0.1µA.
3 The generator uses AC 220 V power supply (AC220V±10%, 50 hz±1%), the ripple factor is less than 0.5%, and can be used for all-weather at the site .
4 High voltage multiplier uses Dupont materials for full solid encapsulation, overcoming the inconvenience brought by the air and oil filled equipment. Broad base and outer cylinder of light quality makes it stand steadily and more convenient for maintenance.
5 75% MOA voltage switch button, simple and convenient testing arrester.
6 Over-voltage setting function displays the over-voltage value during regulation process; perfect protection against discharge of over-voltage, over-current and short circuit. This is the best companion for cable experiments.
7 Perfect break line and non-zero potential start protection function protects the operator and samples at any time. This product has overall design of shock-proof control box, concise, clear panel design and voice prompt for operation.
Product Description
ZGS type DC high voltage generator used AIPWM technique adjusted the inaccuracy linearity of PWM technology let the instrument precision greatly improved. It is mainly used in the electric power department power department of industrial and mining metallurgy iron and steel enterprise for zinc oxide lightning arrester power cables transformers circuit breakers generators and other high voltage electrical equipment of DC withstand voltage test or DC leakage current test.
Product Characteristics
1 Dc high voltage generator adopts high frequency PWM technology to make closed adjustment with high voltage stability, small ripple factor and fast reliable protection circuit. The generator can endure direct discharge by devices of large capacitance. It is of small size and of light weight, convenient for field use.
2 Full range of linear smoothly adjusted voltage, with voltage regulation accuracy smaller than 0.1%; voltage measurement accuracy is 0.5%, resolution 0.1kv; Current measurement accuracy is 0.5%, the minimum resolution: control box 1A, shock resistance current 0.1A.
3 The generator uses AC 220 V power supply (AC220V±10%, 50 hz±1%), the ripple factor is less than 0.5%, and can be used for all-weather at the site .
4 High voltage multiplier uses Dupont materials for full solid encapsulation, overcoming the inconvenience brought by the air and oil filled equipment. Broad base and outer cylinder of light quality makes it stand steadily and more convenient for maintenance.
5 75% MOA voltage switch button, simple and convenient testing arrester.
6 Over-voltage setting function displays the over-voltage value during regulation process; perfect protection against discharge of over-voltage, over-current and short circuit. This is the best companion for cable experiments.
7 Perfect break line and non-zero potential start protection function protects the operator and samples at any time. This product has overall design of shock-proof control box, concise, clear panel design and voice prompt for operation.
Products Introduction
40KV vlf high voltage generator of this product fully complies with the standards of the electric power industry. Mechanical methods are widely used to modulate and demodulate ultra-low frequency signals, but there is no standard sine wave, some errors in high-voltage part measurement and spark discharge. The product can overcome the above shortcomings.
How to choose the suitable products for test ï¼?
Please make sure that the capacitance of test products is below the instrument rated capacitance. The waveform will be influence if the capacitance of test products is too small and the instrument can not normally output when it below 0.05µF. 0.05µF capacitor in parallel to auxiliary output. Below is the capacitance of some instrument for your reference.
ZGS type DC high voltage generator used AIPWM technique adjusted the inaccuracy linearity of PWM technology let the instrument precision greatly improved. It is mainly used in the electric power department power department of industrial and mining metallurgy iron and steel enterprise for zinc oxide lightning arrester power cables transformers circuit breakers generators and other high voltage electrical equipment of DC withstand voltage test or DC leakage current test.
Product Characteristics
1ã??Dc high voltage generator adopts high frequency PWM technology to make closed adjustment with high voltage stability, small ripple factor and fast reliable protection circuit. The generator can endure direct discharge by devices of large capacitance. It is of small size and of light weight, convenient for field use.
40KV vlf high voltage generator of this product fully complies with the standards of the electric power industry. Mechanical methods are widely used to modulate and demodulate ultra-low frequency signals, but there is no standard sine wave, some errors in high-voltage part measurement and spark discharge. The product can overcome the above shortcomings.
How to choose the suitable products for test
Please make sure that the capacitance of test products is below the instrument rated capacitance. The waveform will be influence if the capacitance of test products is too small and the instrument can not normally output when it below 0.05µF. 0.05µF capacitor in parallel to auxiliary output. Below is capacitance of some instrument for your reference.
40KV vlf high voltage generator parameter :
Model
Rated Voltages
Load capacity
Fuse
Weight
Useful
VLF-40
40kV
(peak )
0.1Hz,1.1µF
20A
Control 6
Body Boost 50
Used for cable and generator with corresponding voltage