Lc 141 is single product treatment designed to prevent
Scale deposits and corrosion to ferrous and non-ferrous
Surfaces in hot water heating systems and chilled closed
Loops. It passivates the surfaces and forms a barrier layer to
Inhibit corrosion. It is a synergistic combination of
Phosphonates, polymers and phosphate.
Application
Easily feed/injected directly into the system by means of a chemical by
Pass feeder.
Dosage
Initial treatment is 1 gallon per 1, 000 gallons of water in the system. There
After add lc 141 to maintain a level of 25-35 ppm (mg/l) of
Orthophosphate.
Handling & precaution
It is highly alkaline and should be handled with care to prevent personal
Injury. Protective clothing and eye protection should be provided and worn.
In case of skin contact , immediately flush thoroughly with plenty of clean
Water. In case of eye contact, flush with copious amounts of water for 15
Minutes and obtain immediate medical attention.
Packaging
Available in pail of 20 lt.. Can also be custom packaged.