1) The rated speed : 1500rpm, four strokes, inline. Fan and water tank cooling system, up to the ISO3046 standard
2) The rated output: from 8kW (10kVA) to130kW (162.5kVA)
3) The engine model: 495(Z)D, R4105(Z)D, R6105(Z)(AZL)D, 6113D, 6160D,
6170D
4) The character of the engine:
High efficiency. Low exhaust,good start eddiciency
24V DC start motor
Egnine driven alternator
High pressure oil pump
Turbine charge
Three filters
SAE flywheel shell
THE SPECIFICATIONS OF THE ALTERNATOR:
The world first class alternator, up to the GB755, BS5000, VDE0530, IEC34-1, CSA22.2, AS2359 standard,brushless and self-excitation,it be can supply excitation in many cases:
STAMFORD/ MARATHON/ LEROY SOMER/ QIANGHUI
Standard pitch winding can be inhibit currentf+s nterruption
Insulation Class: H Protection class: H
Frequency at stable state: f_f+1.0%·+
Telephonef+s interference: THF < 2%, TIF < 50·+
THE SPECIFICATIONS OF THE GENERATING SET:
The basic specifications: 230 / 400V AC, 50Hz / 60Hz, 0.8Pf , three phase four wires
Character: base fuel tank for 8 hours
Use: can be used for the open type and the soundproof type , automatic type
Control system:
a) Automatic alarm system: the unit has the acousto-optics alarm
system and arrestor for any situation as the start defeat, the water
is over temperature, the oil pulls down, over speed, over load and
over current
b) Operation display:
i) Unit voltage, tri-phase load current and frequency display
ii) Water temperature, oil pressure display
iii) Fuel level, fuel temperature display
iv) Audible and visual alarm lamps and buzzers
Supply standard collocation:
a) Diesel engine with all accessories, 3 filter, electric systems
b) Alternator
c) Steel structure
d) Fan and water tank cooling system
e) Flange connector
f) 12 / 24V starting motor and charge engine
g) Air cleaner, fuel cleaner, oil cleaner
h) On-board control panel
i) MCCB air conservation switch
j) 12 / 24V starting accumulator and Battery line
k) Set shock absorber
Package: wooden case
EAP 220
Engine:
Engine Model : 1106A-70TAG4
Stand By kVA: 220
Stand By kW : 176
Prime kVA: 200
Prime kW : 160
Rated Current : 288
Engine
heavy duty diesel engine
12V starter and charge alternator
Replaceable air, fuel and oil filters
Mechanical governor control
Tropical type radiator
Flexible fuel hose
Oil drain valve and extension hose
Industrial type silencer and steel compensator
Maintenance-free starter battery
Water jacket heater
1500 rpm engine speed
Alternat
- IP 21-23 Protection Standard
- H Insulation Class
- 50 Hz Frequency
- 4 pole brushless synchronous type alternator
- Automatic Voltage Regulator (AVR)
- 400/230V AC Output Voltage - 1500 rpm
Sound Proof Canopy and Chassis
- Convenient design for easy lifting and carrying
- High standard sound proof canopy design
- Modular design with easily removable nuts - bolts
- Lockable doors
- Transparent window for watching Control Panel
- Electrostatic powder painted, providing protection against harsh weather conditions
- Emergency STOP button
- Fuel tank inside the chassis
- Anti-vibration wedges (engine - chassis and chassis â?? ground)
Optional
- Thermal magnetic CB (for automatic models)
- Super Silent Canopy
- Mobile Generator Sets
- Automatic fuel filling system
- Synchronization panel
- 3 Pole and 4 Pole ATS (Automatic Transfer Switch)
- Fuel Heater, Oil Heater
- External fuel tank and automatic fuel filling system
- Fuel - water separator filter
- Remote monitoring and control system
Engine
Engine Model 1106A-70TAG4
Number of Cylinders 6 Inline
Injection System Direct
Compression Ratio 16:01
Bore 105
Strok 135
Displacement Lt 7,01
Air Intake Turbocharged and air charge cooled
Speed (RPM) 1500
Oil Capacity Lt 18
Standby Power kw / Hp 196.3 / 265
Prime Power Hp 178.9 / 242
Fuel Type Euro Diesel
Governor System Electronic
Cooling System Water Cooling
Coolant Capacity Lt 22
Fuel Consumption (lt / h) Lt Full Load 45,8
Lt %75 LOAD 34,7
Lt %50 LOAD 23,1
Frequency Hz
Power kVA 200
Voltage V 400 V
Number of Phases 3
Automatic Voltage Regulator (A.V.R.) AS440
Voltage Regulation 1%
Insulation Class H
Protection Standard IP22-IP23
Power Factor 0,8
DIMENSIONS
Weight (Silent) Kg 2270
Weight (Open) Kg 1940
Width (Silent) Mm 1200
Length (Silent) Mm 3500
Height (Silent) Mm 1850
Fuel Tank Capacity Lt 360
1 Standby Power : The max power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage. Overloading isn t permissible.
2 Prime Power : The maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load. Average load should be 70%. The generator can be overloaded 10% for 1 hour per 12 hrs.
EAP 200
Engine Model : 1106A-70TAG3
Stand By kVA: 200
Stand By kW : 160
Prime kVA: 182
Prime kW : 145
Rated Current : 262
Engine
heavy duty diesel engine
12V starter and charge alternator
Replaceable air, fuel and oil filters
Mechanical governor control
Tropical type radiator
Flexible fuel hose
Oil drain valve and extension hose
Industrial type silencer and steel compensator
Maintenance-free starter battery
Water jacket heater
1500 rpm engine speed
Alternat
IP 21-23 Protection Standard
H Insulation Class
50 Hz Frequency
4 pole brushless synchronous type alternator
Automatic Voltage Regulator (AVR)
400/230V AC Output Voltage - 1500 rpm
Sound Proof Canopy and Chassis
Convenient design for easy lifting and carrying
High standard sound proof canopy design
Modular design with easily removable nuts - bolts
Lockable doors
Transparent window for watching Control Panel
Electrostatic powder painted, providing protection against harsh weather conditions
Emergency STOP button
Fuel tank inside the chassis
Anti-vibration wedges (engine - chassis and chassis ground)
Optional
- Thermal magnetic CB (for automatic models)
- Super Silent Canopy
- Mobile Generator Sets
- Automatic fuel filling system
- Synchronization panel
- 3 Pole and 4 Pole ATS (Automatic Transfer Switch)
- Fuel Heater, Oil Heater
- External fuel tank and automatic fuel filling system
- Fuel - water separator filter
- Remote monitoring and control system
Engine Model 1106A-70TAG3
Number of Cylinders 6 Inline
Injection System Direct
Compression Ratio 16:01
Bore 105
Strok 135
Displacement Lt 7,01
Air Intake Turbocharged and air charge cooled
Speed (RPM) 1500
Oil Capacity Lt 16,5
Standby Power kw / Hp 180.2 / 243,5
Prime Power Hp 162.7 / 220
Fuel Type Euro Diesel
Governor System Mechanical
Cooling System Water Cooling
Coolant Capacity Lt 22
Fuel Consumption (lt / h) Lt Full Load 41,5
Lt %75 LOAD 31,8
Lt %50 LOAD 20,2
Frequency Hz
Power kVA 200
Voltage V 400 V
Number of Phases 3
Automatic Voltage Regulator (A.V.R.) AS440
Voltage Regulation 1%
Insulation Class H
Protection Standard IP22-IP23
Power Factor 0,8
Weight (Silent) Kg 2190
Weight (Open) Kg 1850
Width (Silent) Mm 1200
Length (Silent) Mm 3500
Height (Silent) Mm 1850
Fuel Tank Capacity Lt 360
1 Standby Power : The max power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage. Overloading isn t permissible.
2 Prime Power : The maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load. Average load should be 70%. The generator can be overloaded 10% for 1 hour per 12 hrs.
EAP 33
Engine: PERKNS
Engine Model : 1103A-33G
Stand By kVA: 33
Stand By kW : 26,4
Prime kVA: 30
Prime kW : 24
Rated Current : 43,2
Engine
heavy duty diesel engine
- 12V starter and charge alternator
- Replaceable air, fuel and oil filters
- Mechanical governor control
- Tropical type radiator
- Flexible fuel hose
- Oil drain valve and extension hose
- Industrial type silencer and steel compensator
- Maintenance-free starter battery
- Water jacket heater
- 1500 rpm engine speed
Alternat
- IP 21-23 Protection Standard
- H Insulation Class
- 50 Hz Frequency
- 4 pole brushless synchronous type alternator
- Automatic Voltage Regulator (AVR)
- 400/230V AC Output Voltage - 1500 rpm
Sound Proof Canopy and Chassis
- Convenient design for easy lifting and carrying
- High standard sound proof canopy design
- Modular design with easily removable nuts - bolts
- Lockable doors
- Transparent window for watching Control Panel
- Electrostatic powder painted, providing protection against harsh weather conditions
- Emergency STOP button
- Fuel tank inside the chassis
- Anti-vibration wedges (engine - chassis and chassis â?? ground)
Optional
- Thermal magnetic CB (for automatic models)
- Super Silent Canopy
- Mobile Generator Sets
- Automatic fuel filling system
- Synchronization panel
- 3 Pole and 4 Pole ATS (Automatic Transfer Switch)
- Fuel Heater, Oil Heater
- External fuel tank and automatic fuel filling system
- Fuel - water separator filter
- Remote monitoring and control system
Engine PERKNS
Engine Model 1103A-33G
Number of Cylinders 3 Inline
Injection System Direct
Compression Ratio 19.25:1
Bore 105
Strok 127
Displacement Lt 3,3
Air Intake Naturally Aspirated
Speed (RPM) 1500
Oil Capacity Lt 8,3
Standby Power kw / Hp 30,4 / 41
Prime Power Hp 27,7 / 37,3
Fuel Type Euro Diesel
Governor System Mechanical
Cooling System Water Cooling
Coolant Capacity Lt 8
Fuel Consumption (lt / h) Lt Full Load 7,2
Lt %75 LOAD 5,6
Lt %50 LOAD 4
Frequency Hz
Power kVA 33
Voltage V 230 / 400 V
Number of Phases 3
Automatic Voltage Regulator (A.V.R.) AS440
Voltage Regulation 1%
Insulation Class H
Protection Standard IP22-IP23
Power Factor 0,8
Weight (Silent) Kg 980
Weight (Open) Kg 825
Width (Silent) Mm 900
Length (Silent) Mm 2200
Height (Silent) Mm 1350
Fuel Tank Capacity Lt 135
1 Standby Power : The max power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage. Overloading isn t permissible.
2 Prime Power : The maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load. Average load should be 70%. The generator can be overloaded 10% for 1 hour per 12 hrs.
FP 250
Engine
Engine Model : 1206A- E70TTAG2
Stand By kVA: 250
Stand By kW : 200
Prime kVA: 227
Prime kW : 182
Rated Current : 327
Engine
heavy duty diesel engine
12V starter and charge alternator
Replaceable air, fuel and oil filters
Mechanical governor control
Tropical type radiator
Flexible fuel hose
Oil drain valve and extension hose
Industrial type silencer and steel compensator
Maintenance-free starter battery
Water jacket heater
1500 rpm engine speed
Alternat
IP 21-23 Protection Standard
H Insulation Class
50 Hz Frequency
4 pole brushless synchronous type alternator
Automatic Voltage Regulator (AVR)
400/230V AC Output Voltage - 1500 rpm
Sound Proof Canopy and Chassis
Convenient design for easy lifting and carrying
High standard sound proof canopy design
Modular design with easily removable nuts - bolts
Lockable doors
Transparent window for watching Control Panel
Electrostatic powder painted, providing protection against harsh weather conditions
Emergency STOP button
Fuel tank inside the chassis
Anti-vibration wedges (engine - chassis and chassis ground)
Optional
- Thermal magnetic CB (for automatic models)
- Super Silent Canopy
- Mobile Generator Sets
- Automatic fuel filling system
- Synchronization panel
- 3 Pole and 4 Pole ATS (Automatic Transfer Switch)
- Fuel Heater, Oil Heater
- External fuel tank and automatic fuel filling system
- Fuel - water separator filter
- Remote monitoring and control system
Engine
Engine Model 1206A- E70TTAG2
Number of Cylinders 6 Inline
Injection System Direct
Compression Ratio 15.08:1
Bore 105
Strok 135
Displacement Lt 7,01
Air Intake Turbocharged aftercooled
Speed (RPM) 1500
Oil Capacity Lt 16,5
Standby Power kw / Hp 226 / 303
Prime Power Hp 204 / 273
Fuel Type Euro Diesel
Governor System Electronic
Cooling System Water Cooling
Coolant Capacity Lt 25
Fuel Consumption (lt / h) Lt Full Load 50,6
Lt %75 LOAD 37,9
Lt %50 LOAD 25,2
Frequency Hz
Power kVA 200
Voltage V 400 V
Number of Phases 3
Automatic Voltage Regulator (A.V.R.) AS440
Voltage Regulation 1%
Insulation Class H
Protection Standard IP22-IP23
Power Factor 0,8
Weight (Silent) Kg 2550
Weight (Open) Kg 2120
Width (Silent) Mm 1300
Length (Silent) Mm 3900
Height (Silent) Mm 1980
Fuel Tank Capacity Lt 450
1 Standby Power : The max power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage. Overloading isn t permissible.
2 Prime Power : The maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load. Average load should be 70%. The generator can be overloaded 10% for 1 hour per 12 hrs.