Conductor is to be sized to carry maximum earth fault current of system at point of application with final conductor temperature not exceeding 160 deg. C (320 deg. F) for at least 5 seconds. Main earthing conductors are to be minimum 120 mm2 or as otherwise required by the particular Section of the Specification.